Part Number: SMX3000RMLV2U
- Draws backup power from hot-swappable, user-replaceable batteries. Add packs to boost runtime capacity.
- Intelligent battery management improves reliability and extends battery life.
- Generator compatible and cold start-capable, so you can deliver clean, uninterrupted power to protected equipment during outages.
- Features a USB port and a SmartSlot internal accessory slot for installing optional cards to enhance performance and manageability.
- Comes with standard 19-inch (48.3-cm) mounting rails, brackets, and hardware.
- Boost and trim automatic voltage regulation (AVR) gives higher application availability by correcting low and high voltage conditions without using the battery.
- Maximizes battery performance, life, and reliability through intelligent precision charging.
- Temperature-compensated battery charging prolongs battery life by regulating the charge voltage according to battery temperature.
- Automatic restart of loads after UPS shutdown.
- Periodic battery self-test ensures early detection of a battery that needs to be replaced.
- Disconnected battery notification warns when a battery is not available to provide backup power.
- Provides remote management of the UPS over the network.
- Audible alarms actively let you know if the unit is on battery, if the battery is low, or if there is an overload condition.
- Serial connectivity provides management of the UPS via a serial port.
- USB connectivity provides management of the UPS via a USB port.
- Disconnected battery notification warns when a battery is not available to provide backup power.
- User-replaceable batteries increase availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR).
- Hot-swappable batteries ensure clean, uninterrupted power to protected equipment while batteries are being replaced.
- Predictive failure notification provides early-warning fault analysis ensuring proactive component replacement.
- Resettable circuit breakers enable a quick recovery from overload events.
- Adjustable voltage-transfer points maximize useful battery life by widening the input voltage window or tightening the output voltage regulation.
- Adjustable voltage sensitivity provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications.
- Field-replaceable power distribution panel ensures compatibility with equipment that has different plug types.
Compliance | |
cUL | 0 |
FCC | |
UL | 0 |
General | |
Adjustable Range for Power Operation | 75-154 V |
Audible Alarms | Alarms indicating battery operation and low battery detection |
Backup Time (Typical) | At full load (2700 W): 5.4 minutes; At half load (1350 watts): 15 minutes |
Battery RBC� Quantity | 1 |
Battery Recharge Time (Typical) | 3 hours |
Battery Type | Maintenance-free sealed lead-acid battery with suspended electrolyte, leakproof |
Configurable Power (Maximum) | 2700 W/3000 VA |
Crest Factor | Up to 5:1 |
Filtering | Full-time multipole noise filtering with 0.3% IEEE surge let-through and zero clamping response time that meets UL® 1449 |
Input (Nominal) | 120 VAC, 50-60 Hz, +/- 3 Hz, autosensing |
Input Voltage | Range for power operations: 82-144 V |
Interface | (1) DB9 F (RS-232) serial port, (1) battery pack port, (1) USB port, (1) SmartSlot card slot, (1) EPO (emergency power off) port |
On-line Thermal Dissipation | 276 BTU/hr. |
Operating Temperature | 32 to 104° F (0 to 40° C) |
Output Frequency (Sync to Mains) | 47-53 Hz for 50 Hz (nominal), 57-63 Hz for 60 Hz (nominal) |
Output Power | 2700 W/3000 VA |
Output Receptacles | (3) NEMA 5-15R, (3) NEMA 5-20R, (1) NEMA L5-30R |
Output Voltage Distortion | Less than 5% at full load |
Output Voltage (Nominal) | 120 V |
RoHS | Yes |
Runtime (Maximum) | 8 hours, 27 minutes |
Surge Energy Rating | 540 joules |
Waveform Type | Sine wave |